These pages quote the manufacturers. Where a manufacturer's public documents do not say something (a file format, a deadline), the page says so instead of filling the gap.
| Program | Headline requirement from its documents |
|---|---|
| Panduit | Passing reports for every link must be received within 6 months of the last test date; files in the tester's own format. |
| CommScope | Documents and test results within 60 days of installation; registration within 90 days; changes within 30 days. |
| Belden | Belden-approved testers only (minimum firmware listed); channel limits; PDF summaries via the Partner Alliance portal. |
| Hubbell | Original raw tester files; PDFs are not accepted. |
Programs we could not source
We publish a requirement only when a manufacturer's own document states it.
- Leviton: Leviton's public warranty information describes eligibility (Certified Integrator/Installer, approved products, registration documents) but states no test-report format or submission deadline that we could find. Source checked.