Hubbell Premise Wiring installation warranty (Mission Critical)

What the installer has to submit, in Hubbell's own words.

Demarc › Manufacturer programs › Hubbell

Source documents read 2026-10-18. Page last updated 2026-10-19. Manufacturers revise these documents: confirm the current version with the program before you rely on a date or a number.

Hubbell's form is short and specific. The detail that catches installers: it wants the original raw tester files and says PDFs will not be accepted.

Requirements, with the manufacturer's wording

TopicWhat it says
Test files Send the original raw data tester files only, for Category 5e, 6 and 6A copper. Converted files, PDFs included, are not accepted.
“Send the original raw data tester file(s) only. Do not convert the test results into another format. PDFs, etc. will not be accepted.”
Source: Registration for Installation Warranty, Mission Critical (Hubbell Premise Wiring)
Approved testers Fluke OmniScanners, DSX 5000, DTX 1800 and 4000 Series, DSP 4000 Series; Ideal LANTEK 6 and 7 Series; Viavi Certifier 10G and 40G; PSiber LanExpert 80T and 85; Softing WireXpert 4500.
“Approved Testers: Fluke: OmniScanners Fluke: DSX 5000 Fluke: DTX 1800, 4000 Series Fluke: DSP 4000 Series Ideal: LANTEK 6 & 7 Series Viavi: Certifier 10G & 40G PSiber: LanExpert 80T and 85 Softing: WireXpert 4500 WX4500”
Source: Registration for Installation Warranty, Mission Critical (Hubbell Premise Wiring)
Fiber Include all optical fiber results from a power meter accurate to +/-0.5 dB or better, in original tester format; backbone results should include the allowable attenuation calculated with the link attenuation equation.
“Include all optical fiber test results (if applicable) from a power meter with an accuracy of + .5 dB or better in its original tester format.”
Source: Registration for Installation Warranty, Mission Critical (Hubbell Premise Wiring)
Forms and schematics Complete the Structured Cabling System Registration Request, with installer company information, cable manufacturer and type, project information and products installed, plus both the Horizontal Schematic and Backbone Schematic forms.
“Complete both the Horizontal Schematic and Backbone Schematic forms.”
Source: Registration for Installation Warranty, Mission Critical (Hubbell Premise Wiring)
Project contacts Incomplete project or end-user contact details can get the documents refused for signature.
“End Users may refuse to sign warranty documents when this information is incorrect or incomplete, which results in delays in processing.”
Source: Registration for Installation Warranty, Mission Critical (Hubbell Premise Wiring)
Where By email to the address on the form, or upload to a file-sharing site and email the link for large files. Forms are on Hubbell's Premise Wiring site under Mission Critical Installer, Warranty Forms.
“For large files, please upload to a file sharing site like dropbox.com, one drive, etc. and email the link.”
Source: Registration for Installation Warranty, Mission Critical (Hubbell Premise Wiring)
What the public documents do not say
  • The form states no submission deadline and no link-versus-channel rule.

Check your export against this program

Drop a LinkWare CSV export into the free checker. It looks for failing and marginal links, links with no result, duplicate IDs, mixed test limits and missing fields, and applies the rules above that can be read from a file. The file stays in your browser.

What Demarc does for this program

Demarc prepares the package; you submit it through Hubbell warranty desk (its registration form directs submission by email or a file-sharing link). For this program the Demarc warranty kit checks:

Deadline: no deadline published by Hubbell; check your RSP agreement. Demarc shows no countdown for Hubbell.

Copper test configuration in Demarc's kit for Hubbell. Hubbell's public documents state no permanent-link or channel rule, so the kit does not assume one: you choose the configuration you tested on the project, the kit checks every copper result against that choice, and it tells you to confirm it with Hubbell.